Response timeout means a response was not returned after sending data to the Controller for a ES100X Controller Terminal (Block Model 045). The manual's first action is: “Communications will be stopped with the specified ES100X and tried with another ES100X. Check the communications path, the communications settings (7 data bits, even parity, and 2 stop bits), and other required settings in the ES100X (parameter setting mode, unit number, etc.).”
- Model
- Omron CS1W-LCB01 and CS1W-LCB05
- Display shows
- Response timeout (30)
- Type
- Error code
- Source
- Manual p. 186
What 30 means
Response timeout p. 186
Common causes
- A response was not returned after sending data to the Controller for a ES100X Controller Terminal (Block Model 045). (Response was not returned for 5 s 3 times.) p. 186
What to do
- Communications will be stopped with the specified ES100X and tried with another ES100X. Check the communications path, the communications settings (7 data bits, even parity, and 2 stop bits), and other required settings in the ES100X (parameter setting mode, unit number, etc.). p. 186
Before you service the product, read the safety instructions in the manual p. 11.
If 30 is still not resolved
The manual gives no further instruction for this code. Open the code table in the PDF or contact Omron service.
This page summarises what the manufacturer’s manual says about 30; each statement links to the page it comes from, and quoted lines are copied word for word. It is not a substitute for the manual or for a qualified installer. ManualLib is not affiliated with Omron. Found a mistake? Report an error.