One of the following problems was detected during a cold start. 1) The data was corrupted by noise or other factor. 2) The power was interrupted during a backup. The manual's first action is: “Execute the [Download] or [Clear all] operation from CX-Process Tool Version 3.0. The Flash Memory Data Error Flag (A42403) will go OFF if the data in RAM becomes valid.”
- Model
- Omron CS1W-LCB01 and CS1W-LCB05
- Display shows
- Parameter backup data (flash memory) error (0331)
- Type
- Error code
- Source
- Manual p. 184
What 0331 means
Parameter backup data (flash memory) error p. 184
Common causes
- One of the following problems was detected during a cold start. 1) The data was corrupted by noise or other factor. 2) The power was interrupted during a backup. Note: If the function block database (RAM) is valid, the data will be backed up when power is turned ON again. p. 184
What to do
- Execute the [Download] or [Clear all] operation from CX-Process Tool Version 3.0. The Flash Memory Data Error Flag (A42403) will go OFF if the data in RAM becomes valid. p. 184
Before you service the product, read the safety instructions in the manual p. 11.
If 0331 is still not resolved
The manual gives no further instruction for this code. Open the code table in the PDF or contact Omron service.
This page summarises what the manufacturer’s manual says about 0331; each statement links to the page it comes from, and quoted lines are copied word for word. It is not a substitute for the manual or for a qualified installer. ManualLib is not affiliated with Omron. Found a mistake? Report an error.