Omron CS1W-LCB01 and CS1W-LCB05 Error 19: Inappropriate operation

Omron CS1W-LCB01 and CS1W-LCB05 Loop Control Board · taken from the manufacturer’s manual, pages cited

Error code19

Two or more S1 to S3 select switches are set to 1 (ON) at the same time in the 3-output Selector block (Block Model 163) or 3-input Selector block (Block Model 164). The manual's first action is: “The output value that was active before the error occurred is held. Re-program the Step Ladder Program block so that S1 to S3 select switches are set to 1 (ON) independent of each other.”

Model
Omron CS1W-LCB01 and CS1W-LCB05
Display shows
Inappropriate operation (19)
Type
Error code
Source
Manual p. 186

What 19 means

Inappropriate operation p. 186

Common causes

  • Two or more S1 to S3 select switches are set to 1 (ON) at the same time in the 3-output Selector block (Block Model 163) or 3-input Selector block (Block Model 164). p. 186
  • There is a syntax error in Arithmetic Operation (Block Model 126), the THEN or ELSE expression is not defined, or the output reverse scaling limits are not set. p. 186
  • There are syntax errors in the membership functions or rules for the Fuzzy Logic block (Block Model 016) making execution impossible. p. 186
  • a) A value does not have one sign character and 5 or fewer numeric characters (e.g., when a + sign is included). p. 186
  • b) Values are not separated by colons. p. 186
  • c) The values that have been set are insufficient. p. 186
  • d) There are more than three critical points in a membership functions. p. 186
  • e) Critical points in membership functions do not rise to the right. p. 186
  • f) Membership functions are not set for labels specified in rules (NL, NS, ZR, PS, PL). p. 186

What to do

  1. The output value that was active before the error occurred is held. Re-program the Step Ladder Program block so that S1 to S3 select switches are set to 1 (ON) independent of each other. p. 186
  2. Execution of the Arithmetic Operation block will be stopped. Check the contents of the conditional statement and calculation expressions and check the settings of the output reverse scaling limits. p. 186
  3. Operation of the Fuzzy Logic block will stop. Check the membership functions and rules. The ITEM number where the problem occurred is given in ITEM 006 (Operation Error Details). p. 186

Before you service the product, read the safety instructions in the manual p. 11.

If 19 is still not resolved

The manual gives no further instruction for this code. Open the code table in the PDF or contact Omron service.