Omron CS1W-LCB01 and CS1W-LCB05 Error 29: Reception error for external device

Omron CS1W-LCB01 and CS1W-LCB05 Loop Control Board · taken from the manufacturer’s manual, pages cited

Error code29

A communications frame error was generated by the data received from an ES100X Controller for an ES100X Controller Terminal (Block Model 045). The manual's first action is: “Communications will be stopped with the specified ES100X and tried with another ES100X. Check the communications path and the communications settings (7 data bits, even parity, and 2 stop bits).”

Model
Omron CS1W-LCB01 and CS1W-LCB05
Display shows
Reception error for external device (29)
Type
Error code
Source
Manual p. 186

What 29 means

Reception error for external device p. 186

Common causes

  • A communications frame error was generated by the data received from an ES100X Controller for an ES100X Controller Terminal (Block Model 045). (An FCS check error or frame error occurred 3 times in a row.) p. 186

What to do

  1. Communications will be stopped with the specified ES100X and tried with another ES100X. Check the communications path and the communications settings (7 data bits, even parity, and 2 stop bits). p. 186

Before you service the product, read the safety instructions in the manual p. 11.

If 29 is still not resolved

The manual gives no further instruction for this code. Open the code table in the PDF or contact Omron service.