Mitsubishi Electric MDS-C1 Series Error 3A: Overcurrent

AC Servo/Spindle · taken from the manufacturer’s manual, pages cited

Error code3A

Excessive motor drive current was detected, possibly causing vibration or no vibration at all. The manual's first action is: “PR”

Model
Mitsubishi Electric MDS-C1 Series
Display shows
Overcurrent (3A)
Type
Error code
Source
Manual p. 310

What 3A means

Overcurrent p. 310

Common causes

  • An excessive current was detected in the motor drive current. p. 310
  • Vibration is occurring. p. 310
  • There is no vibration. p. 310
  • The speed loop gain (SV005) setting is larger than the standard value. p. 310
  • The setting is approximately the same as the standard value. p. 310
  • Check the current loop gain. (SV009, SV010, SV011, SV012) p. 310
  • The standard value is set. p. 310
  • Disconnect the UVW phase wiring from the terminal block, and the cannon plug from the motor. Check the insulation with a tester. p. 310
  • There is no problem. p. 310
  • Check the insulation between the motor power cable and FG. p. 310
  • There is a ground fault at the power cable. p. 310
  • Connect the cannon plug, and check the insulation between the power cable and FG. p. 310
  • Check if there are any abnormality in the motor's ambient environment. (Ex. Ambient temperature, cutting water) p. 310

What to do

  1. PR p. 310
  2. Set a filter. Lower the speed loop gain (SV005). p. 310
  3. Investigate item 2. p. 310
  4. Set an appropriate value. p. 310
  5. Investigate item 3. p. 310
  6. Set the standard value. p. 310
  7. Investigate item 4. p. 310
  8. Replace the motor power cable. p. 310
  9. Investigate item 5. p. 310
  10. Investigate item 6. p. 310
  11. Replace the motor. (With the absolute position system, the zero point must be established.) p. 310
  12. Investigate item 7. p. 310
  13. Improve the installation environment. (With the absolute position system, the zero point must be established.) p. 310

Before you service the product, read the safety instructions in the manual p. 4.

If 3A is still not resolved

  • contact service / dealer p. 5
    “Wiring, maintenance and inspection work must be done by a qualified technician.”

This page summarises what the manufacturer’s manual says about 3A; each statement links to the page it comes from, and quoted lines are copied word for word. It is not a substitute for the manual or for a qualified installer. ManualLib is not affiliated with Mitsubishi Electric. Found a mistake? Report an error.