Fault codeEr.120
This code indicates product matching fault, which can be caused by motor and drive power rating mismatch, unsupported component type connected, or improper combination of products. The manual's first action is: “NO.1”
- Model
- Inovance ISMH/ISMV series
- Display shows
- Product matching fault (Er.120)
- Type
- Fault code
- Source
- Manual p. 184
What Er.120 means
Product matching fault p. 184
Common causes
- Motor and drive power rating (rated voltage) mismatch, or unsupported component type (e.g., encoder) is connected p. 184
- Improper combination of products, e.g., motor and drive power rating mismatch p. 184
- Connected an encoder type not supported by the selected drive (e.g., A/A type drive does not support absolute encoder) p. 184
What to do
- NO.1 p. 184
- Check whether the motor's rated current is within the drive's current rating p. 184
- Refer to the user manual to confirm whether the selected drive type and its supported encoder types include this encoder p. 184
- Select the correct encoder type or replace with a different type of drive p. 184
Before you service the product, read the safety instructions in the manual p. 186.
If Er.120 is still not resolved
This page summarises what the manufacturer’s manual says about Er.120; each statement links to the page it comes from, and quoted lines are copied word for word. It is not a substitute for the manual or for a qualified installer. ManualLib is not affiliated with Inovance. Found a mistake? Report an error.