An undervoltage error occurs when the main circuit voltage is below its minimum specified value or there is no input voltage. The manual's first action is: “Check whether the wiring of main circuit input voltage is correct. Reconfirm voltage wiring. Correct input wiring is needed.”
- Model
- Delta ASDA-B series
- Display shows
- Undervoltage (ALE 3)
- Type
- Error code
- Source
- Manual p. 256
What ALE 3 means
Undervoltage p. 259
Common causes
- Main circuit voltage is below its minimum specified value. p. 259
- The main circuit voltage is below its minimum specified value. p. 259
- No input voltage at main circuit. p. 259
- Power input error. (Incorrect power input) p. 259
- Servo drive hardware is damaged. p. 259
What to do
- Check whether the wiring of main circuit input voltage is correct. Reconfirm voltage wiring. Correct input wiring is needed. p. 259
- Use voltmeter to check whether input voltage at main circuit is normal. Reconfirm power supply, including switches. p. 259
- Use voltmeter to check whether the input voltage is within the specified limit. Use correct power supply or stabilizing power. p. 259
- The servo drive hardware is damaged after the users have used voltmeter to check the input voltage falls within the rated input voltage. Please contact your distributor for assistance or contact with Delta. p. 259
- This fault message can be removed automatically after the voltage has returned within its specification. p. 259
Before you service the product, read the safety instructions in the manual p. 3.
If ALE 3 is still not resolved
The manual gives no further instruction for this code. Open the code table in the PDF or contact Delta service.
This page summarises what the manufacturer’s manual says about ALE 3; each statement links to the page it comes from, and quoted lines are copied word for word. It is not a substitute for the manual or for a qualified installer. ManualLib is not affiliated with Delta. Found a mistake? Report an error.