Code 0024 means the motor is turning faster than the highest allowed speed because of incorrectly set minimum/maximum speed, insufficient braking torque or changes in load when using torque reference. The manual's first action is: “Check minimum/maximum frequency settings. Check adequacy of motor braking torque. Check applicability of torque control. Check need for brake chopper and resistor(s).”
- Model
- ABB ACS355
- Display shows
- OVERSPEED (7310) 0306 bit 7 (0024)
- Type
- Fault code
- Source
- Manual p. 347
What 0024 means
OVERSPEED (7310) 0306 bit 7 p. 347
Common causes
- Motor is turning faster than highest allowed speed due to incorrectly set minimum/maximum speed, insufficient braking torque or changes in load when using torque reference. Operating range limits are set by parameters 2001 MINIMUM SPEED and 2002 MAXIMUM SPEED (in vector control) or 2007 MINIMUM FREQ and 2008 MAXIMUM FREQ (in scalar control). p. 347
What to do
- Check minimum/maximum frequency settings. Check adequacy of motor braking torque. Check applicability of torque control. Check need for brake chopper and resistor(s). p. 347
Before you service the product, read the safety instructions in the manual p. 239.
If 0024 is still not resolved
- contact your local ABB representative p. 19 “contact your local ABB representative or Authorized Service Center for replacement”