ABB ACS355 Error 0003: DEV OVERTEMP (4210) 0305 bit 2

ABB ACS355 drive · taken from the manufacturer’s manual, pages cited

Fault code0003

Code 0003 means the drive IGBT temperature is excessive, with a fault trip limit of 135 °C. The manual's first action is: “Check ambient conditions. See also section Derating on page 359.”

Model
ABB ACS355
Display shows
DEV OVERTEMP (4210) 0305 bit 2 (0003)
Type
Fault code
Source
Manual p. 344

What 0003 means

DEV OVERTEMP (4210) 0305 bit 2 p. 344

Common causes

  • Drive IGBT temperature is excessive. Fault trip limit is 135 °C. p. 344

What to do

  1. Check ambient conditions. See also section Derating on page 359. p. 344
  2. Check air flow and fan operation. p. 344
  3. Check motor power against drive power. p. 344

Before you service the product, read the safety instructions in the manual p. 239.

If 0003 is still not resolved

  • contact your local ABB representative p. 19
    “contact your local ABB representative or Authorized Service Center for replacement”