Fault code0003
Code 0003 means the drive IGBT temperature is excessive, with a fault trip limit of 135 °C. The manual's first action is: “Check ambient conditions. See also section Derating on page 359.”
- Model
- ABB ACS355
- Display shows
- DEV OVERTEMP (4210) 0305 bit 2 (0003)
- Type
- Fault code
- Source
- Manual p. 344
What 0003 means
DEV OVERTEMP (4210) 0305 bit 2 p. 344
Common causes
- Drive IGBT temperature is excessive. Fault trip limit is 135 °C. p. 344
What to do
- Check ambient conditions. See also section Derating on page 359. p. 344
- Check air flow and fan operation. p. 344
- Check motor power against drive power. p. 344
Before you service the product, read the safety instructions in the manual p. 239.
If 0003 is still not resolved
- contact your local ABB representative p. 19 “contact your local ABB representative or Authorized Service Center for replacement”