ABB ACS355 Error 0006: DC UNDERVOLT (3220) 0305 bit 5

ABB ACS355 drive · taken from the manufacturer’s manual, pages cited

Fault code0006

Code 0006 means intermediate circuit DC voltage is not sufficient because of a missing input power line phase, blown fuse, rectifier bridge internal fault or too low power. The manual's first action is: “Check that undervoltage controller is on (parameter 2006 UNDERVOLT CTRL).”

Model
ABB ACS355
Display shows
DC UNDERVOLT (3220) 0305 bit 5 (0006)
Type
Fault code
Source
Manual p. 344

What 0006 means

DC UNDERVOLT (3220) 0305 bit 5 p. 344

Common causes

  • Intermediate circuit DC voltage is not sufficient due to missing input power line phase, blown fuse, rectifier bridge internal fault or too low power. p. 344

What to do

  1. Check that undervoltage controller is on (parameter 2006 UNDERVOLT CTRL). p. 344
  2. Check input power supply and fuses. p. 344

Before you service the product, read the safety instructions in the manual p. 239.

If 0006 is still not resolved

  • contact your local ABB representative p. 19
    “contact your local ABB representative or Authorized Service Center for replacement”

This page summarises what the manufacturer’s manual says about 0006; each statement links to the page it comes from, and quoted lines are copied word for word. It is not a substitute for the manual or for a qualified installer. ManualLib is not affiliated with ABB. Found a mistake? Report an error.