ABB ACS355 Error 0002: DC OVERVOLT (3210) 0305 bit 1

ABB ACS355 drive · taken from the manufacturer’s manual, pages cited

Fault code0002

Code 0002 means excessive intermediate circuit DC voltage, with a DC overvoltage trip limit of 420 V for 200 V drives and 840 V for 400 V drives. The manual's first action is: “Check that overvoltage controller is on (parameter 2005 OVERVOLT CTRL).”

Model
ABB ACS355
Display shows
DC OVERVOLT (3210) 0305 bit 1 (0002)
Type
Fault code
Source
Manual p. 344

What 0002 means

DC OVERVOLT (3210) 0305 bit 1 p. 344

Common causes

  • Excessive intermediate circuit DC voltage. DC overvoltage trip limit is 420 V for 200 V drives and 840 V for 400 V drives. p. 344

What to do

  1. Check that overvoltage controller is on (parameter 2005 OVERVOLT CTRL). p. 344
  2. Check input power line for static or transient overvoltage. p. 344
  3. Check brake chopper and resistor (if used). DC overvoltage control must be deactivated when brake chopper and resistor is used. p. 344
  4. Check deceleration time (2203, 2206). Retrofit frequency converter with brake chopper and brake resistor. p. 344

Before you service the product, read the safety instructions in the manual p. 239.

If 0002 is still not resolved

  • contact your local ABB representative p. 19
    “contact your local ABB representative or Authorized Service Center for replacement”

This page summarises what the manufacturer’s manual says about 0002; each statement links to the page it comes from, and quoted lines are copied word for word. It is not a substitute for the manual or for a qualified installer. ManualLib is not affiliated with ABB. Found a mistake? Report an error.