Fault code0002
Code 0002 means excessive intermediate circuit DC voltage, with a DC overvoltage trip limit of 420 V for 200 V drives and 840 V for 400 V drives. The manual's first action is: “Check that overvoltage controller is on (parameter 2005 OVERVOLT CTRL).”
- Model
- ABB ACS355
- Display shows
- DC OVERVOLT (3210) 0305 bit 1 (0002)
- Type
- Fault code
- Source
- Manual p. 344
What 0002 means
DC OVERVOLT (3210) 0305 bit 1 p. 344
Common causes
- Excessive intermediate circuit DC voltage. DC overvoltage trip limit is 420 V for 200 V drives and 840 V for 400 V drives. p. 344
What to do
- Check that overvoltage controller is on (parameter 2005 OVERVOLT CTRL). p. 344
- Check input power line for static or transient overvoltage. p. 344
- Check brake chopper and resistor (if used). DC overvoltage control must be deactivated when brake chopper and resistor is used. p. 344
- Check deceleration time (2203, 2206). Retrofit frequency converter with brake chopper and brake resistor. p. 344
Before you service the product, read the safety instructions in the manual p. 239.
If 0002 is still not resolved
- contact your local ABB representative p. 19 “contact your local ABB representative or Authorized Service Center for replacement”