Code 0028 means a fieldbus communication break, with parameter 5306 EFB OK MESSAGES and 5307 EFB CRC ERRORS values remaining unchanged when there is no master device on line and the parameter 5307 EFB CRC ERRORS value increasing with every read/write command when two or more devices have the same address. The manual's first action is: “Check status of fieldbus communication. See chapter Fieldbus control with embedded fieldbus on page 301, chapter Fieldbus control with fieldbus adapter on page 325 or appropriate fieldbus adapter manual. Check fault function parameter settings. Check connections. Check if master can communicate.”
- Model
- ABB ACS355
- Display shows
- 0028
- Type
- Fault code
- Source
- Manual p. 347
What 0028 means
SERIAL 1 ERR (7510) 0306 bit 11 (programmable fault function 3018, 3019) p. 347
Common causes
- Fieldbus communication break p. 347
- If there is no master device on line, parameter 5306 EFB OK MESSAGES and 5307 EFB CRC ERRORS values remain unchanged. p. 347
- If two or more devices have the same address, parameter 5307 EFB CRC ERRORS value increases with every read/write command. p. 347
- If the communication wires are swapped (terminal A on one device is connected to terminal B on another device), parameter 5306 EFB OK MESSAGES S value remains unchanged and parameter 5307 EFB CRC ERRORS increases. p. 347
What to do
- Check status of fieldbus communication. See chapter Fieldbus control with embedded fieldbus on page 301, chapter Fieldbus control with fieldbus adapter on page 325 or appropriate fieldbus adapter manual. Check fault function parameter settings. Check connections. Check if master can communicate. p. 347
- Check that the network master is connected and properly configured. Check the cable connection. p. 347
- Check the device addresses. No two devices on line may have the same address. p. 347
- Check the RS-232/EIA-485 interface connection. p. 347
Before you service the product, read the safety instructions in the manual p. 239.
If 0028 is still not resolved
- contact your local ABB representative p. 19 “contact your local ABB representative or Authorized Service Center for replacement”
This page summarises what the manufacturer’s manual says about 0028; each statement links to the page it comes from, and quoted lines are copied word for word. It is not a substitute for the manual or for a qualified installer. ManualLib is not affiliated with ABB. Found a mistake? Report an error.