User manual for the Yamatake AUD10C2100 phototube unit covering safety precautions, replacement procedures, and operation verification.
The Yamatake AUD10C2100 phototube unit detects ultraviolet radiation from combustion flames and is used in combination with the AUD300C2100 advanced UV sensor. The manual provides safety warnings, part identification, replacement steps, and verification methods for maintenance personnel.
It specifies a service life of less than 3 years or 25,000 hours, requires a tightening torque of 0.7 N·m for screws, and describes flame voltage verification using a multimeter connected to the AUR controller terminals 9 and 10. The document also references related manuals for the AUR300C and AUR350C controllers. This manual is written in Chinese.
| Service Life | Less than 3 years or 25,000 hours |
|---|---|
| Tightening Torque | 0.7 N·m |
| Recommended Flame Voltage | DC 2.0–4.0 V (1.5 s flame response) |
| Operating Temperature Limit (AUD300C2100) | 100 °C maximum |
The phototube unit has an effective service life of less than 3 years or 25,000 hours.
Tighten terminal screws and mounting screws to 0.7 N·m.
Connect a multimeter to AUR controller terminals 9 (+) and 10 (-), ignite a flame at the UV sensor's light-receiving part, and confirm the output flame voltage.
The recommended flame voltage is DC 2.0–4.0 V with a flame response of 1.5 seconds.