The Yamatake AUD10C2100 phototube unit detects ultraviolet radiation from combustion flames and is used in combination with the AUD300C2100 advanced UV sensor. The manual provides safety warnings, part identification, replacement steps, and verification methods for maintenance personnel.

It specifies a service life of less than 3 years or 25,000 hours, requires a tightening torque of 0.7 N·m for screws, and describes flame voltage verification using a multimeter connected to the AUR controller terminals 9 and 10. The document also references related manuals for the AUR300C and AUR350C controllers. This manual is written in Chinese.

What's inside

  • Safety Precautions
  • Overview
  • Part Names
  • Phototube Unit Replacement
  • Operation Verification
  • Inspection and Adjustment

Specifications

Service LifeLess than 3 years or 25,000 hours
Tightening Torque0.7 N·m
Recommended Flame VoltageDC 2.0–4.0 V (1.5 s flame response)
Operating Temperature Limit (AUD300C2100)100 °C maximum

Frequently asked questions

What is the service life of the AUD10C2100 phototube unit?

The phototube unit has an effective service life of less than 3 years or 25,000 hours.

What torque should be applied to the terminal and mounting screws?

Tighten terminal screws and mounting screws to 0.7 N·m.

How do you verify the operation of the phototube unit?

Connect a multimeter to AUR controller terminals 9 (+) and 10 (-), ignite a flame at the UV sensor's light-receiving part, and confirm the output flame voltage.

What is the recommended flame voltage range for verification?

The recommended flame voltage is DC 2.0–4.0 V with a flame response of 1.5 seconds.