This document describes the specifications and instructions for use of the ACTIVALTM electric three-way valve VY54X0L (JIS 10K-FC200). The product features a compact and lightweight design, with the valve and actuator integrated into one device. It can be operated using different control signals, including nominal 135 Ω feedback potentiometer, nominal 135 Ω resistance input, 4-20 mA DC input, 2-10 V DC input, and 0-10 V DC input. The product is durable, low power consumption, and has linear characteristics. It is suitable for general air conditioning control.
The document provides a comprehensive user guide for the ACTIVAL VY54X0L electric three-way valve series. This compact device integrates the valve and actuator into a single unit, designed to control cold or hot water with a rated pressure meeting JIS 10K standards. The actuator features a reversible synchronous motor that operates at low voltage (24 V AC) and supports various control signals including potentiometers, current loops, and voltage inputs for proportional control. This manual is written in Chinese.
| Rated Pressure | JIS 10K (Max 0.98 MPa) |
|---|---|
| Nominal Size | DN50, DN65, DN80 |
| Power Supply | 24 V AC ± 15 % 50 Hz/60 Hz |
| Operating Temperature Range | 0 °C to 100 °C |
| Flow Characteristic | Linear characteristic |
| Control Signals Supported | 135 Ω Potentiometer, 4-20 mA DC, 2-10 V DC, 0-10 V DC |
| Valve Body Material | Gray Cast Iron (JIS FC200) |
The valve body rated pressure is JIS 10K, with a maximum pressure of 0.98 MPa.
The valve supports a nominal 135 Ω feedback potentiometer, 4-20 mA DC input, and 2-10 V or 0-10 V DC inputs.
The allowable fluid temperature ranges from 0 °C to 100 °C. The fluid must not be frozen.
Yes, it can be installed from vertical to side positions. However, if installed outdoors, it must always be in a vertical position.