Hioki 3157-01 AC Grounding HiTester measures protective grounding resistance with high AC current and supports multiple safety standards.
The Hioki 3157-01 AC Grounding HiTester is designed to measure whether the metal enclosure of electrical equipment is connected to the ground terminal at sufficiently low resistance. It can also evaluate grounding conditions of large-scale electrical installations by passing a high AC current and measuring the voltage drop.
The unit supports measurement as prescribed by multiple safety standards and includes constant-current testing up to 31.0 A, a test data count function, storage for up to 20 settings, soft start, and a fluorescent tube display. It has compact dimensions of about 320 x 90 x 263 mm and a mass of about 7 kg.
| Resistance measurement range | 0 to 1.800 Ω (0.001 Ω resolution) |
|---|---|
| Resistance measurement accuracy | ±(2% rdg. +4 dgt.) after zero-adjust |
| Current monitoring range | 0 to 35.0 A AC (0.1 A resolution) |
| Current monitoring accuracy | ±(1% rdg. +5 dgt.) at 3 A or more |
| Voltage monitor range | 0 to 6.00 V AC (single range, 0.01 V resolution) |
| Voltage monitor accuracy | ±(1% rdg. +5 dgt.) |
| Current setting range | 3.0 A to 31.0 A AC (0.1 A resolution), into 0.1 Ω load |
| Maximum output power | 130 VA (at output terminals) |
| Open-terminal voltage | Max. 6 V AC |
| Generator frequency | 50 Hz or 60 Hz sine wave (selectable) |
| Dimensions | Approx. 320 (W) x 90 (H) x 263 (D) mm |
| Mass | Approx. 7 kg (246.9 oz) without options |
| Power supply voltage range | 100 - 120 V/200 - 240 V AC (switching) |
| Power line frequency | 50 - 60 Hz |
| Ambient operating conditions | 0 to +40 °C, 90% rh or less (no condensation) |
It supports IEC60065, IEC60204-1, IEC60335-1, IEC60601-1, IEC60950, IEC61010-1, and UL standard 1.
0 to 1.800 Ω with 0.001 Ω resolution.
3.0 A to 31.0 A AC into a 0.1 Ω load.
It has external I/O and a front EXT connector, with optional RS-232C or GP-IB.