About this manual

The FAFNIR VPI is an interface converter with eight intrinsically safe sensor circuits. It is used to supply intrinsically safe sensors in potentially explosive atmospheres and to convert electrical signals between non-intrinsically safe and intrinsically safe areas; it is mainly used as part of tank content measurement. The VPI-Supply power supply is used to power the converter.

The manual covers ABNT NBR IEC 60079-0:2020 and ABNT NBR IEC 60079-11:2013, safety instructions, mounting and disassembly, installation and terminal assignments, device identification, technical data, and special conditions of use. The devices have IP00 protection and an ambient temperature range of -20 °C to +60 °C; they must be installed in an enclosure with at least IP20 protection, and a minimum 50 mm gap is required between the VPI and VPI-Supply. This manual is written in Portuguese.

What's inside

  • Area of application
  • Standards
  • Safety instructions
  • Use
  • Mounting and disassembly
  • Installation
  • Terminal designations
  • Device identification
  • Technical data
  • Special conditions of use

Specifications

Ambient temperature range-20 °C … +60 °C
Degree of protectionIP00
Number of intrinsically safe sensor circuits8
VPI-Supply auxiliary supply230 VAC ± 10 %; 50 Hz … 60 Hz
VPI-Supply output voltage12 VDC ± 5 %
VPI auxiliary supply12 VDC ± 5 %
Ex marking[Ex ia Ga] IIC [Ex ia Da] IIIC
Certificate No.UL-BR 17.0875X
VPI converters per VPI-Supply2

Frequently asked questions

What is the VPI interface converter used for?

It is used to supply intrinsically safe sensors that can be used in potentially explosive atmospheres.

What is the ambient temperature range?

The ambient temperature range is -20 °C to +60 °C.

What is the output voltage of the VPI-Supply?

The output voltage is 12 VDC ± 5 %.

What minimum enclosure protection is required for installation?

The interface converter must be installed in an enclosure with at least IP20 protection.