This document introduces the safety manual for FAFNIR's LS 300 and LS 500 H SIL sensors, which are suitable for areas that require safety assessment according to EN 61508
This document serves as a safety manual for the FAFNIR LS 300 level detector and LS 500 H SIL measuring transducer series. It details the application of these devices in safety-related subsystems requiring SIL 2 compliance according to EN 61508, specifically for overfill and dry-running protection.
| Response time (dry-run protection) | approximately 20 s |
|---|---|
| Vibration test range | 10 Hz to 55 Hz and 2 g |
| Mean time to restoration | 8 h |
| Interval of the retest | 1 year |
The resistance value must be less than 30 Ω (or < 2.5 Ω with firmware version 1.0.1.255).
The functionality should be checked at appropriate intervals, but at least once a year.
It switches to the "immersed" state after less than a second and the sensor relay is deactivated.