This is the safety manual of TORRIX … & VISY-Stick … 44 799 13752002, which mainly introduces the safety characteristics of the product. It is suitable for use in security subsystems with a safety level of SIL 2
This document is a safety manual for FAFNIR TORRIX and VISY-Stick series magnetostrictive level sensors. It details the application domain, specifically for safety systems conforming to the EN 61508 SIL 2 standard. The manual covers various sensor types, including those for biodiesel, ethanol, LPG, and interstitial monitoring, and specifies hardware and software version requirements for safe operation. This manual is written in French.
| Safety Integrity Level | SIL 2 |
|---|---|
| Mean Time To Repair | 8 hours |
| Safety Test Interval | 1 year |
| Architecture | 1001 |
The sensors are designed for safety systems conforming to the EN 61508 SIL 2 standard.
This manual applies to all level sensors starting from hardware version 4.
The safety state is reached within ten seconds when an error is detected.