Troubleshooting reference manual for an Enphase microinverter system, covering Enlighten alerts, Envoy communications, and PV production issues.
This reference manual describes troubleshooting flows and procedures for an Enphase microinverter installation. It covers Enlighten messages and alerts, Envoy and communications issues, and microinverter/PV module issues, plus power production.
The alert section includes ACFOOR, ACVOOR, Critical Temperature, Grid Gone, and Zigbee device messages. The communications section covers Envoy networking and power line communication, and the production section covers low or zero production and Enlighten production history.
| Nominal frequency range (M190, M210, D380) | 59.3 to 60.5; typical 60.0 |
|---|---|
| Acceptable AC voltage, 240 VAC split phase, L1 to L2 | 211 to 264 Vac |
| Acceptable AC voltage, 208 VAC three phase, L1 to L2 to L3 | 183 to 229 Vac |
| Recommended AC branch voltage drop | Less than 1.5 volts or 0.6 percent |
| Anti-islanding export stop time | Within two seconds |
ACFOOR stands for AC Frequency Out of Range.
It protects against continuous inverter operation while isolated from the utility; if utility power is disconnected, the inverter stops exporting power within two seconds.
No action is required unless the condition persists; if it persists, contact Enphase Energy customer support.
The acceptable L1 to L2 range is 211 to 264 Vac.