Operation and installation manual for Delta H2.5, H3, H3A, H4A and H5A single-phase grid-tie transformerless solar inverters, covering wiring, power control…
This manual covers the installation, operation, maintenance and technical data of the Delta H2.5 / H3 / H3A / H4A / H5A grid-tie transformerless solar inverters. The device is a single-phase (L + N + PE) solar inverter that converts DC power from a PV array into single-phase AC to supply loads and feed excess power back to the local grid. It uses a DSP design and does not support off-grid operation.
The manual includes safety warnings, unpacking and package inspection, mounting and wiring instructions (AC grid connection, DC connection from the PV array, and PE connection), start-up and shutdown procedures, optional active/reactive power control and LVRT functions, error messages and troubleshooting, and de-commissioning. Installation and start-up must be carried out by an accredited technician or certified electrician.
| Power rating | 2.5kVA (H2.5), 3kVA (H3/H3A), 4kVA (H4A), 5kVA (H5A) |
|---|---|
| Maximum efficiency | >97.4% (>98.3% @ H5A) |
| Europe efficiency | 96.8% (98.0% @ H5A) |
| Reactive power capability | Cap 0.8 – Ind 0.8 |
| Total harmonic distortion | < 3% @ full load |
| Grid type | Single-phase (L + N + PE), grid-tie, transformerless |
| Upstream AC circuit breaker (H5A _222) | 25A for 5 kVA |
No, the manual states that this device does not support off-grid function.
Installation and start-up must be carried out by an accredited technician, and installation may only be conducted by certified electricians.
Dangerous voltage is present for 1 minute after disconnecting all sources of power; 5 minutes is recommended for discharging.
No. The inverter contains no user-serviceable parts, and opening it will void the warranty; repair work should only be carried out by the manufacturer.