Carlo Gavazzi DPA51/DPA71 are 3-phase voltage monitoring relays for industrial motor protection, detecting phase loss and sequence errors with DIN-rail…
The DPA51 and DPA71 are 3-phase mains monitoring relays designed for DIN-rail mounting in industrial applications. They monitor phase loss and phase sequence using the monitored power supply. The DPA51 has one changeover relay output, while the DPA71 has two. Both models feature wide voltage ranges, LED status indicators, and regenerated voltage detection for accurate phase loss detection even during motor operation.
Models are available in different voltage ranges: DPA71DM23 (208–240V), DPA51CM44 (208–480V), and DPA71DM48 (380–480V). They are rated for AC1 and DC12/13 contacts, with electrical lifetimes of 50,000 operations and mechanical lifetimes exceeding 30 million operations. The devices are housed in compact enclosures (17.5mm and 35.5mm) and are rated for operation from -20°C to 60°C for DPA51 and -20°C to 50°C for DPA71.
| Voltage Range | DPA71DM23: 208–240VAC ±15% (177–276V), DPA51CM44: 208–480VAC ±15% (177–552V), DPA71DM48: 380–480VAC ±15% (323–552V) |
|---|---|
| Output Type | DPA51: SPDT changeover relay, DPA71: DPDT changeover relay |
| Contact Rating | DPA51: AC1 5A@250VAC, DC12 5A@24VDC, AC15 2.5A@250VAC, DC13 2.5A@24VDC; DPA71: AC1 5A@250VAC, AC15 3A@250VAC, DC13 2A@24VDC |
| Dimensions | DPA51: 17.5x81x67.2mm, DPA71: 35.5x81x67.2mm |
| Operating Temperature | DPA51: -20 to 60°C, DPA71: -20 to 50°C |
| Housing Material | Polyamide (PA66/6) or Phenylene ether+Polystyrene (PPE-PS) |
| Protection Degree | IP20 |
| Electrical Lifetime | ≥50x10³ operations (at 5A, 250V, cosφ=1) |
| Mechanical Lifetime | >30x10⁶ operations |
| Mounting Type | DIN-rail |
DPA71DM23 supports 208–240VAC ±15%, DPA51CM44 supports 208–480VAC ±15%, and DPA71DM48 supports 380–480VAC ±15%.
DPA51 has a single SPDT changeover relay output, while DPA71 has a dual DPDT changeover relay output.
DPA51 operates from -20°C to 60°C, while DPA71 operates from -20°C to 50°C.
The electrical lifetime is ≥50,000 operations at 5A and 250V with cosφ=1.