AUMA PF-Q80 – PF-Q600 Part-Turn Actuators Technical Data

Technical data and specifications for AUMA PF-Q80 and PF-Q600 part-turn actuators designed for open-close and modulating duty applications.


AUMA PF-Q80 – PF-Q600 Part-Turn Actuators Technical Data - cover page
Brand
AUMA
Category
Other
Document type
Product Leaflet
Language
English
Pages
4
File format
PDF
File size
135 KB
Published
27 October, 2026
Updated
27 October, 2026
MD5 checksum
166FCFBE7CFE1BA19160E1FEBD8B0B33

About this manual

This document provides technical data and specifications for AUMA PF-Q80 and PF-Q600 part-turn actuators. These actuators are equipped with integral controls and are designed for open-close and modulating duty applications, featuring variable speed brushless motors and adjustable torque settings.

What's inside

  • General information
  • Features and functions
  • Bluetooth Communication interface
  • Electrical connection
  • Operation and Display
  • Configuration
  • Monitoring
  • Service conditions
  • Dimensions
  • Electrical data

Specifications

Duty Class (Open-close)Class C according to EN 15714-2, intermittent duty S4 - 50 %
Duty Class (Modulating)Class A and B according to EN 15714-2, short-time duty S2 - 15 min
Motor TypeVariable speed, brushless motor
Motor ProtectionYes, at standstill with spring-applied brake
Standard Swing Angle120° ±15°
Standard Voltage1-phase AC current: 100 – 240 V / 50 – 60 Hz
Option VoltageDC current: 24 V DC ±10 %
Operating Altitude≤ 2,000 m above sea level
HumidityUp to 100 % relative humidity
Enclosure ProtectionIP67
Pollution Degree (External)4 (when closed)
Operating Cycles (Modulating)1.8 million steps

Frequently asked questions

What is the standard swing angle for these actuators?

The standard swing angle is 120° ±15° adjustable between min. and max. values with mechanical end stops.

Can the operating time be selected?

Yes, the operating time can be selected in 9 levels when placing the order and is settable via Bluetooth in steps of 1 %.

What is the maximum permissible torque for modulating duty?

The values from the column 'Torque range' still apply as tripping torques for modulating duty.

Is the actuator suitable for use in areas with high salinity?

Yes, it is suitable for use in areas with high salinity, almost permanent condensation, and high pollution.