Installation and operation guide for Argus Cordex 48-1kW 19" Shelf, including specs, safety, and technical data.
This manual provides installation, operation, and fault diagnosis instructions for the Argus Cordex 48-1kW 19" Shelf system. It includes detailed specifications for the shelf and its rectifier module, safety standards, environmental ratings, and EMC compliance. The system supports up to 3000W and is designed for flush mounting in 19" racks. Technical details cover electrical inputs, output voltage, dimensions, and mounting requirements.
The manual references additional documents for full installation guidance, including schematics, customer connections, and warranty information. It also outlines safety certifications such as CSA, UL, and CE, and provides environmental operating conditions from -40°C to 65°C and up to 4000m elevation.
| Maximum Output | 62.4A, 58Vdc |
|---|---|
| Recommended Feeder Breaker | 15A, #12AWG |
| Mechanical Dimensions | 177.1mm H x 444.5mm W x 303.4mm D |
| Weight | 7.3 kg (16 lb.) |
| Input Voltage | 17 to 65Vdc |
| MTBF | >430,000 hours @ 30°C |
| Output Voltage | 40.5 to 58Vdc |
| Maximum Power | 1000W continuous/module |
| Operating Temperature | -40 to 65°C |
| Humidity | 0 to 95% non-condensing |
| Elevation | -500 to +4000m |
Maximum Output: 62.4A, 58Vdc.
Operating temperature: -40 to 65°C standard @ 3000m, derated to 55°C @ 4000m.
MTBF: >430,000 hours @ 30°C (86°F).
Maximum Power: 1000W continuous/module.