Siemens QFM66 Wind Tube Sensor Manual

The QFM66 duct sensor is used to measure relative humidity (high precision) and temperature in ducts. The sensor can be used to control the humidity in supply or return air ducts, or to limit the maximum value of the humidity of the supply air after the steam humidifier.


Brand
Siemens
Category
Other
Document type
User Manual
Language
Chinese
Pages
4
File format
PDF
File size
280 KB
Updated
30 September, 2023
MD5 checksum
557FF5187BEEB028FE967F151CCD3829

About this manual

The QFM66 sensor measures relative humidity (0‑100 % RH) and temperature (0‑50 °C and –35‑+35 °C) in ventilation and air‑conditioning ducts. It outputs two independent DC 0‑10 V signals for each measurement range and complies with EN 60730, EN 61000‑6‑2 and IP65 protection.

The manual covers ordering information, mechanical design, electrical connections, installation guidelines, commissioning steps, and safety requirements. It also lists technical specifications such as power supply (AC 24 V ±20 %), power consumption (≤1 VA), cable length limits, and environmental ratings. This manual is written in Chinese.

What's inside

  • Technical Data
  • Mechanical Design
  • Installation Guidelines
  • Commissioning Notes
  • Product Safety
  • Electrical Connections

Specifications

Humidity measurement range0 %‑100 % RH
Temperature measurement range (signal B2)0 °C‑50 °C
Temperature measurement range (signal B3)-35 °C‑+35 °C
Power supply voltageAC 24 V ±20 %
IP protection ratingIP65
Sensor head operating temperature range-40 °C‑+80 °C
Maximum cable length (1.5 mm²)150 m

Frequently asked questions

What humidity range does the QFM66 sensor cover?

It measures relative humidity from 0 % to 100 % RH.

How far must the sensor be installed from a steam humidifier?

The minimum distance is 3 m and the maximum distance is 10 m.

What power supply does the sensor require?

It requires an AC 24 V supply with a tolerance of ±20 %.

Download PDF (280 KB)