Siemens RCC20 Room Temperature Controller User Manual

RCC20 room temperature controller is used for independent room temperature control of two-pipe fan coil units with electric heaters for heating and cooling. It can output switching signals to valve actuators and electric heaters, and output switching signals to three-speed fans. RCC20 can be controlled according to room or return air temperature, and has automatic cold/hot conversion, working mode switching input, optional control parameters, AC230V working voltage and other features.


Brand
Siemens
Category
Industrial Supply
Document type
User Manual
Language
Chinese
Pages
10
File format
PDF
File size
295 KB
Updated
30 September, 2023
Model
RCC20
MD5 checksum
55540B22BF48E6A49EC42E62576D51A5

About this manual

This manual provides detailed information on the RCC20 room temperature controller, including its heating and cooling functions, selectable operating modes, and wiring connections. It also describes the controller's built‑in and optional temperature sensors and how to configure DIP switches for various features.

Installation guidelines cover mounting height, wiring practices, and safety precautions, while the technical data section lists electrical ratings, temperature ranges, and performance parameters. The document includes wiring diagrams and a parts list for accessories such as sensors and actuators. This manual is written in Chinese.

What's inside

  • Features
  • Heating and Cooling Modes
  • Operating Modes
  • Technical Data
  • Installation and Commissioning
  • Engineering Notes
  • Wiring Diagram
  • Accessories

Specifications

Working voltageAC230V ±10/‑15%
Frequency50‑60 Hz
Maximum power consumption6 VA
Set‑point range8 °C – 30 °C
Control accuracy at 25 °C±0.7 K
Heating conversion error1 K or 4 K
Cooling conversion error0.5 K or 2 K
Normal mode deadband2 K or 5 K
Energy‑saving heating set‑point16 °C
Energy‑saving cooling set‑point28 °C
Standby mode set‑point8 °C
Weight0.23 kg
Enclosure colourWhite

Frequently asked questions

How does the RCC20 switch between heating and cooling modes?

The controller automatically changes mode when the measured temperature deviates from the set‑point by half the conversion error; heating uses a 1 K or 4 K error, cooling uses 0.5 K or 2 K.

How is fan speed controlled?

Fan speed is set by the three output contacts Q1, Q2 and Q3; each output selects a different speed level.

What power supply is required for the RCC20?

The controller requires an AC 230 V supply with a tolerance of ±10 % to ‑15 %.

Download PDF (295 KB)

More Siemens Manuals


View all Siemens manuals →