Siemens RDU50 HVAC Temperature Controller User Manual

RDU50 is a room temperature controller with a liquid crystal display from Siemens Building Technologies for heating or cooling systems, with PI control, 0 to 10V output to the actuator, automatic cold/hot conversion, manual cold/hot conversion, operating modes: normal, energy-saving or off, operating mode conversion input, adjustable installation and control parameters, output reverse signal, display of room temperature and optional temperature values, minimum and maximum temperature set value limitation and other features.


Brand
Siemens
Category
Other
Document type
User Manual
Language
English
Pages
10
File format
PDF
File size
284 KB
Updated
01 October, 2023
MD5 checksum
B485DDD0EAB8445B5548BC5F0FC6041F

About this manual

This manual describes the functions of the RDU50 room temperature controller, including PI control, automatic or manual heating/cooling switching, and a LCD display of room temperature and setpoints. It also lists the supported output ranges (0‑10 V) and compatible devices such as VAV controllers and valve actuators.

Installation instructions cover mounting height, wiring, DIP switch settings, and sensor calibration. Parameter tables show how to adjust operating modes, temperature limits, and control gains, and explain how settings are retained after power loss.

What's inside

  • Functions
  • Operating Modes
  • Settings and Parameters
  • Installation and Commissioning
  • Technical Data
  • Accessories
  • Mechanical Design
  • Sensor Calibration

Specifications

Power supply voltage24 V ±20%
Control output voltage range0–10 V DC
Maximum power consumption4 VA
Maximum relative humidity<95 % RH
Storage temperature range-20 to +70 °C
Weight0.23 kg

Frequently asked questions

How does the RDU50 automatically switch between heating and cooling?

It uses an automatic switching sensor (QAH11.1+ARG86.3) that measures water temperature; above 28 °C it switches to heating, below 16 °C it switches to cooling.

How can the output signal be inverted?

Set DIP2 to ON for normal polarity (0 V = 0 %, 10 V = 100 %) or to OFF for reversed polarity (0 V = 100 %, 10 V = 0 %).

Are the controller settings retained after power loss?

Yes, all configured control parameters remain stored even when the power is cut.

How do you change a parameter on the RDU50?

Press the “+” and “‑” keys together for 3‑5 seconds, release, then press “+” for 3 seconds to display the parameter (e.g., P01). Use “+” and “‑” to adjust the value.