Yaskawa Varispeed F7 (BTOP-S616-55A) Variable Frequency Drive Technical Manual

This manual describes the features and specifications of the YASKAWA BTOP-S616-55A variable frequency drive.


Yaskawa Varispeed F7 (BTOP-S616-55A) Variable Frequency Drive Technical Manual - cover page
Brand
YASKAWA
Category
inverter
Document type
User Manual
Language
Portuguese
Pages
187
File format
PDF
File size
3.9 MB
Published
29 November, 2023
Updated
29 November, 2023
MD5 checksum
286D32E6E2898CF23DCD373FD4199C7E

About this manual

This technical manual applies to the Yaskawa Varispeed F7 variable frequency drive (Drive F7, model CIMR-F7). It covers safety precautions, introduction, drive load selection, and standard drive specifications for the 208-240 V and 480 V classes.

The manual lists electrical ratings such as output frequency, output voltage, input voltage and frequency, voltage and frequency fluctuation limits, overload capability, and carrier frequency. This manual is written in Portuguese.

What's inside

  • Safety precautions (Precauções e Cuidados)
  • Introduction (Introdução)
  • Drive load selection (Seleção da carga do Drive)
  • Standard drive specifications, 208-240 V (Especificações do Drive 208-240Vac)
  • Standard drive specifications, 480 V (Especificações do Drive 480Vac)

Specifications

Maximum output frequency400.0 Hz
Maximum output voltage, 208-240 V class200, 208, 220, 230, or 240 VAC, three-phase
Maximum output voltage, 480 V class380, 400, 415, 440, 460, or 480 VAC, three-phase
Nominal input voltage, 208-240 V class200/208/220/230/240 VAC, 50/60 Hz, three-phase
Nominal input voltage, 480 V class380/400/415/440/460/480 VAC, 50/60 Hz, three-phase
Allowed input voltage fluctuation+10%, -15%
Allowed input frequency fluctuation±5%
Heavy-duty overload rating150% of rated current for 60 seconds
Normal-duty overload ratingApproximately 110% for 1 minute
Carrier frequency, heavy duty2 kHz

Frequently asked questions

What is the maximum output frequency of the drive?

The maximum output frequency is 400.0 Hz.

What input voltage fluctuation is allowed?

The allowed input voltage fluctuation is +10% and -15%.

What input frequency fluctuation is allowed?

The allowed input frequency fluctuation is ±5%.

What is the heavy-duty overload rating?

The heavy-duty overload rating is 150% of rated current for 60 seconds.

Download PDF (3.9 MB)