The IS-3 pressure transmitter is suitable for SIL2 applications in the process industry for operating modes with low demand rate.
This document is an addition to the operating instructions for the IS-3 pressure transmitter. It gives safety-related data for functional safety in the process industry and in machine building, plus operating conditions and electromagnetic-environment conditions.
English, German, French, and Spanish versions are included. The stated data cover measuring range ≤ 1,000 bar, SIL2 suitability, HFT 0, SFF 64 %, PFDa 1.75 x 10-4, proof test interval 1 year, and MTTFd 1254 years.
| Measuring range | ≤ 1,000 bar |
|---|---|
| Device type | B |
| HFT (Hardware Fault Tolerance) | 0 |
| SFF (Safe Failure Fraction) | 64 % |
| λtotal (Total Failure Rate) | 126 FIT |
| λNE (No Effect Failure Rate) | 8 FIT |
| λSU (Safe Undetected Failure Rate) | 27 FIT |
| λDD (Dangerous Detected Failure Rate) | 51 FIT |
| λDU (Dangerous Undetected Failure Rate) | 40 FIT |
| PFDa (Average Probability of Failure on Demand) | 1.75 x 10-4 |
| Tproof (Proof Test Interval) | 1 year |
| Safety Integrity Level | SIL 2 |
| MTTFd (Mean Time To Dangerous Failure) | 1254 years |
| Diagnosis | none |
| Mean ambient temperature | max. 40 °C |
| Interference immunity | 1 kV |
It is suitable for SIL2 applications in the process industry for operating modes with a low demand rate, and MTTFd values are available for machine-building applications.
The proof test interval is 1 year.
The MTTFd value is 1254 years.
No. For safety applications, hydrogen is not permissible as a medium.