Data sheet for the Beck 990 Display differential pressure transmitter with technical data, pressure ranges, order matrix, accessories and connection diagram.
The Beck 990 Display series differential pressure transmitter measures differential pressure, overpressure and vacuum in gaseous, non-combustible and non-aggressive media. It offers one adjustable pressure range (from 100% down to 50% of full scale via the menu), switchable display units (kPa, mbar or inWC), a switchable output signal of 0...10 V or 4...20 mA, an adjustable response time from 0.1 to 20 s, and two adjustable potential-free switching outputs (S1 up to 50 VAC/5 A, S2 up to 250 VAC/5 A).
Typical applications include building automation and air conditioning systems, overpressure measurement in clean rooms and laboratories, constant pressure measurement in VAV applications, and dynamic filter and ventilator monitoring. The document lists technical data, available pressure ranges from 0...25 Pa to 0...250 kPa, an order matrix for the 990M (manual offset calibration) and 990A (automatic zero offset compensation) variants, accessories such as Climaset hose kits, and a connection diagram with dimensional drawings.
| Supply voltage | 18 ... 30 VAC / VDC |
|---|---|
| Output signal | 0 ... 10 V or 4 ... 20 mA |
| Medium | Air and non-combustible and non-aggressive gases |
| Linearity | ≤ ±0.5% FS, min. ±1 Pa |
| Uncertainty | ±1% FS, min. ±1 Pa |
| Humidity | 0 ... 95% rel, non-condensing |
| Measuring method | Piezoresistive pressure transducer |
| Process connection | 4 mm and 6 mm hose connection |
| Display | Red 7 segment LED display, 4 digits |
| Housing dimensions | 143 x 96 x 48 mm |
| Weight | approx. 230 g |
| Switching output S1 | max. 50 VAC/5 A |
| Switching output S2 | max. 250 VAC/5 A |
The output signal can be switched in the menu between 0...10 V and 4...20 mA.
Three units can be selected in the menu: Pascal (kPa, factory setting), mbar or inWC.
The 990M can be re-calibrated to zero in the menu in a pressureless state, while the 990A performs an automated zero offset compensation.
Yes, the output signal shape can be changed in the menu from linear to square rooted to enable volume flow measurement via a differential pressure reading.