The Mitsubishi Electric MELSEC iQ-F FX5 Micro PLC User's Manual (CC-Link IE TSN Edition) describes the features and functions of the Mitsubishi Electric Micro PLC.
This is the CC-Link IE TSN edition of the user's manual for the Mitsubishi Electric MELSEC iQ-F FX5 series micro programmable controller. The extracted pages contain the safety section that opens the manual, together with a short note on using an industrial switching hub that supports CC-Link IE TSN Class B when connecting CC-Link IE TSN modules.
The manual groups its instructions under warning and caution headings: precautions for use, setting, network security, installation, wiring, startup and maintenance, disposal and transport. Within these it gives concrete requirements such as wire ratings, grounding, screwdriver size and separation distances for power and communication cabling, and it directs readers to the CPU module user's manual (hardware edition) for general specifications. This manual is written in Chinese.
| Wire temperature rating | 80 °C or higher |
|---|---|
| Grounding | 2 mm² or more wire, D-class grounding, ground resistance 100 Ω or less |
| Terminal screwdriver | No. 2 Phillips screwdriver with head width 6 mm or less |
| Separation from main circuit and power lines | At least 100 mm |
All external power supplies must be switched off before installation, wiring or other work is started, otherwise there is a risk of electric shock or product damage.
Wiring with a rated temperature of 80 °C or higher must be used.
They must not be bundled or run close together with the main circuit or power lines; a distance of at least 100 mm is required.
During installation and wiring the protective film prevents cuttings and wire debris from entering the ventilation holes, and it must be removed after the work is finished so that heat can dissipate.