The manual provides installation, operation, maintenance, safety instructions, specifications, and fault codes for the Mitsubishi Electric 2033 G Series UPS.
This technical manual is intended for owners and service personnel of the Mitsubishi Electric 2033 G Series Uninterruptible Power Supply. It covers safety precautions, installation procedures, operating controls, specifications, fault diagnosis, parts replacement, and warranty information.
The document includes detailed environmental requirements, recommended circuit breaker ratings, power specifications, battery details, and a comprehensive fault‑code list to aid troubleshooting and ensure reliable operation of the UPS.
| Rated Output kVA | 30, 50 |
|---|---|
| Rated Output kW | 24, 40 |
| Input Voltage | 120/208 V +15% ~ -25% |
| Frequency | 60 Hz ±5% |
| Battery Type | VRLA |
| Nominal Battery Voltage | 432 Vdc |
| Power Factor (nominal) | 0.8 |
| Inverter Overload Capability | 150 % for 1 minute |
The manual specifies a minimum temperature of 32 °F (0 °C) and a maximum of 104 °F (40 °C) for the installation environment.
Fault code UF003 signals a "Converter abnormal" condition and requires contacting a service engineer.