Micro830™ 10-Point Programmable Controller Catalog Number 2080-LC30-10QWB, 2080-LC30-10QVB
This installation guide covers the Rockwell Automation Micro830 10-point programmable controllers with catalog numbers 2080-LC30-10QWB and 2080-LC30-10QVB. It includes important user information, environmental and cabinet requirements, electrostatic discharge precautions, hazardous location information, and connection and power supply requirements.
The guide also lists related resources and identifies the controller as an open-type device for use in a suitable cabinet. It states requirements such as pollution degree 2, overvoltage category II, operation below 2000 m without derating, Group 1 Class A EMC classification, hazardous location marking CL I, DIV 2, GP A, B, C, D, a 3.0 m maximum USB/serial cable length, no more than two wires per terminal, and SELV/PELV or Class 2 power supplies. This manual is written in Chinese.
| Catalog numbers | 2080-LC30-10QWB, 2080-LC30-10QVB |
|---|---|
| Pollution degree | 2 |
| Overvoltage category | II |
| Altitude without derating | Below 2000 m (6562 ft) |
| EMC classification | Group 1, Class A industrial device per IEC/CISPR 11 |
| Enclosure type | Open type device; must be installed in a suitable cabinet |
| Hazardous location marking | CL I, DIV 2, GP A, B, C, D |
| Maximum USB/serial cable length | 3.0 m (9.84 ft) |
| Maximum wires per terminal | 2 |
| Power supply for CE LVD | SELV or PELV |
| Power supply for UL | Class 2 |
USB and serial cables must not exceed 3.0 m (9.84 ft).
No more than two wires can be connected to a single terminal.
The power supply must be SELV or PELV.
The device must be powered by a Class 2 power supply.