This manual describes the installation and commissioning of Vacon NX AC drives and NXS/P drives enclosures IP21 and IP54.
This User's Manual covers the Vacon NX series frequency converters, NXS/P models in IP21 and IP54 enclosures. It provides the information needed to install, commission and operate the drive, including safety instructions, EU directive and CE/EMC information, delivery checks, technical data, mounting and cooling, power and control cabling, keypad navigation, commissioning steps and fault tracing.
The manual opens with a start-up quick guide of ten mandatory steps, from checking the delivery and reading the safety instructions through cable and fuse sizing, keypad language and application selection, motor rating plate data entry, and final commissioning. It also notes that all parameters are explained in the All in One Application Manual and that the document is available in paper and electronic editions.
| Mains voltage (Vacon NX_2) | 208–240 V |
|---|---|
| Mains voltage (Vacon NX_5) | 380–500 V |
| Mains voltage (Vacon NX_6) | 525–690 V |
| Earth leakage current | Exceeds 3.5 mA AC |
| Enclosure protection classes | IP21 and IP54 |
Wait until the fan stops and the keypad indicators go out, then wait 5 more minutes before doing any work on the Vacon NX_ connections.
Check the rating plate values for the motor's nominal voltage, frequency, speed, current and cos ϕ, and enter them in parameter group G2.1.
If a fault protection relay is used, it must be at least type B, preferably B+ (according to EN 50178), with a trip level of 300 mA.
No, only spare parts delivered by Vacon can be used.