Mitsubishi Air Conditioner Compressor Error Code List and Troubleshooting Guide

This document describes the fault codes and solutions for Mitsubishi air conditioners.


Mitsubishi Air Conditioner Compressor Error Code List and Troubleshooting Guide - cover page
Brand
Mitsubishi
Category
Other device
Document type
Service Manual
Language
English
Pages
16
File format
PDF
File size
239 KB
Published
15 November, 2023
Updated
15 November, 2023
MD5 checksum
FFD4DACA8D7781B09CD71A762196F990

About this manual

This document is an error code list and troubleshooting guide for the compressor of a Mitsubishi air conditioning / refrigeration unit. It tables error codes E01 through E82 with the anomaly item, detection condition, action taken during detection (all stop, compressor stop, fan stop or indication only), recovery condition, whether an external alarm and communication output occur, and whether recovery is manual (operate the S1 operation switch or reset the power) or automatic.

The second part gives troubleshooting for each error code, listing the detected content, probable causes (such as disconnected sensor connectors, sensor failure or a failed control PCB CS1-PCB), checks to perform, and corrective actions including reconnecting connectors, replacing sensors, the electronic expansion valve (MOV3), the compressor or the control PCB. Codes covered include high pressure anomaly, discharge gas temperature anomaly, pressure and temperature sensor anomalies, inverter and communication anomalies, fan motor anomalies and refrigerant shortage alarms.

What's inside

  • Error Code List
  • Troubleshooting for Each Error Code
  • Failure Diagnosis
  • Method of Checking Sensor Characteristics
  • Method of Checking Coil Resistance of Electronic Expansion Valve

Specifications

High pressure trip threshold11.7 MPa or over
Inverter overload trip threshold9 Arms or above
Refrigerant flood back alarm conditionSuction gas superheat 1 K or below for 2 min
Refrigerant shortage alarm conditionExpansion valve opening 180 step for 10 min
Inverter communication anomaly detectionNo signals for 25 sec

Frequently asked questions

How do I recover from error code E01 (high pressure anomaly, 7th trip)?

Recovery is manual: operate the S1 operation switch or reset the power.

What are the probable causes of error code E04 (discharge gas temperature sensor anomaly)?

A disconnected or loose discharge gas temperature sensor connector (2P6), a failed sensor, or a failed control PCB (CS1-PCB).

Does error code E31 recover automatically?

Yes, E31 (high pressure anomaly, 1st to 6th trip) auto-restarts after stopping for 5 minutes.

Download PDF (239 KB)

More Mitsubishi Manuals


View all Mitsubishi manuals →