This document describes the fault codes and solutions for Mitsubishi air conditioners.
This document is an error code list and troubleshooting guide for the compressor of a Mitsubishi air conditioning / refrigeration unit. It tables error codes E01 through E82 with the anomaly item, detection condition, action taken during detection (all stop, compressor stop, fan stop or indication only), recovery condition, whether an external alarm and communication output occur, and whether recovery is manual (operate the S1 operation switch or reset the power) or automatic.
The second part gives troubleshooting for each error code, listing the detected content, probable causes (such as disconnected sensor connectors, sensor failure or a failed control PCB CS1-PCB), checks to perform, and corrective actions including reconnecting connectors, replacing sensors, the electronic expansion valve (MOV3), the compressor or the control PCB. Codes covered include high pressure anomaly, discharge gas temperature anomaly, pressure and temperature sensor anomalies, inverter and communication anomalies, fan motor anomalies and refrigerant shortage alarms.
| High pressure trip threshold | 11.7 MPa or over |
|---|---|
| Inverter overload trip threshold | 9 Arms or above |
| Refrigerant flood back alarm condition | Suction gas superheat 1 K or below for 2 min |
| Refrigerant shortage alarm condition | Expansion valve opening 180 step for 10 min |
| Inverter communication anomaly detection | No signals for 25 sec |
Recovery is manual: operate the S1 operation switch or reset the power.
A disconnected or loose discharge gas temperature sensor connector (2P6), a failed sensor, or a failed control PCB (CS1-PCB).
Yes, E31 (high pressure anomaly, 1st to 6th trip) auto-restarts after stopping for 5 minutes.