The GasSens Gas Detection System is a system used to detect chlorine gas. The system consists of an A11 Sensor/Transmitter, an A14 Receiver Module, an A17 Power Supply Module, NEMA 4X Enclosures, Explosion-Proof Enclosures, an Audible Horn, a Strobe Lamp, an A19 Battery Back-up, etc.
This O & M Manual covers the GasSens gas detection system from Analytical Technology, Inc. (ATI), an on-line monitoring system for detecting hazardous gases in ambient air. This edition focuses on the chlorine gas monitor and describes the system's modular components: the A11 sensor/transmitter, A14 receiver module, A17 power supply module, NEMA 4X and explosion-proof enclosures, audible horn, strobe lamp, and A19 battery back-up.
The manual includes a table of gases the system can monitor with standard, minimum, and maximum ranges, followed by mechanical and electrical installation instructions, receiver module configuration and operation, power supply details, troubleshooting, parts lists, and optional equipment such as the battery backup and strobe light.
| A17 power supply input | 85-270 V AC (50/60 Hz) or DC |
|---|---|
| Chlorine standard range | 0-10 PPM |
| Battery back-up | 12 VDC, 4 AH |
| Receiver distance from sensor | up to 1000 feet |
| Strobe flash rate | approximately 70 flashes per minute |
| Explosion-proof enclosure rating | Class 1, Division 1, Groups C & D |
GasSens systems are available for a variety of gases including ammonia, carbon monoxide, chlorine, ozone, hydrogen sulfide, sulfur dioxide, oxygen, and hydride gases such as arsine and phosphine, each with standard, minimum, and maximum ranges listed in Table 1-1.
The A17 accepts any AC (50 or 60 Hz) or DC voltage between 85 and 270 volts and is self-regulating, requiring no jumper or switch changes.
The sensor/transmitter is mounted in the hazard area and the receiver can be located anywhere within 1000 feet.
The optional A19 battery back-up connects to the A17 power supply module and provides standby power so that detection continues uninterrupted.