This document describes the single-phase ARD series elevator emergency self-rescue device, which can help the elevator to operate safely in the event of a power failure.
This manual (version V2.6) describes the ARD series single-phase elevator power-failure self-rescue device (停电自救援装置). When the mains supply fails, the device disconnects the elevator system from the grid and, after roughly 13 seconds, generates single-phase AC220V or AC380V power so the elevator can run at self-rescue speed and level to release passengers. A single rescue run lasts up to 5 minutes before the output shuts off automatically.
The manual explains the model numbering system (ARD4S/2S/2D/2E variants with or without battery), the nameplate, standard specifications, product selection tables for motor power and elevator load ratings, mounting dimensions for wall-mounted and floor-standing installation, application wiring diagrams for each series including the ARD4SXX-Z variant, and operation of the panel with its LED indicators, start button, enable switch and 4-digit display. This manual is written in Chinese.
| Recommended self-rescue speed | 1/12 of elevator rated speed |
|---|---|
| Single run time | 5 min |
| Output voltage waveform | Sine wave |
| Cooling method | Natural / forced air cooling |
| Protection rating | IP20 |
| Ambient conditions | -15~40°C, humidity below 90%RH (non-condensing) |
| Vibration | Above 1G below 20Hz |
| Motor power range (380V class) | 5.5 kW – 37 kW |
After the mains supply is cut, the device disconnects the elevator from the grid and produces single-phase AC220V or AC380V output in about 13 seconds.
A single rescue run lasts at most 5 minutes, after which the output is cut off automatically.
C. means charging (shows battery voltage), P. means normal output (shows output voltage), E. means fault (shows fault code), and B. shows battery level as a percentage.
The ARD4SXX-Z scheme is intended for systems where the inverter supply front end has a contactor (emergency-stop or power-on main contactor).