This document is the instruction manual for three-phase intelligent voltage meter, which introduces the basic function, technical parameters, parameter setting and panel operation of the product.
ELC EVR-GHLC-3P and EVR-GHLC-3PP are three-phase intelligent voltage meters with overvoltage, undervoltage, phase loss, phase sequence, and three-phase voltage imbalance detection. They include an internal alarm buzzer and output relays; undervoltage, phase sequence, and imbalance detection are optional, and reset can be automatic or manual.
The manual describes panel operation, parameter settings, terminal wiring, fault codes, and Modbus RTU communication over RS485, including register access and exception codes. This manual is written in Chinese.
| Measurement range (EVR-GHLC-3P) | 55-500 VAC |
|---|---|
| Measurement range (EVR-GHLC-3PP) | 0-500 VAC |
| Relay action delay | 0-99.9 s |
| Output relay contacts | 2 NO and 2 NC |
| Output relay capacity | 7 A/250 VAC or 7 A/30 VDC |
| Installation | 35 mm DIN rail |
| Dimensions | 107 mm x 93 mm x 59 mm |
| Weight | <400 g |
| Operating environment | Temperature -20 to 60 C, humidity 10 to 85% |
| Communication interface | RS485 |
| Communication distance | 1000 m maximum |
| Default baud rate | 9600 bps |
The EVR-GHLC-3PP measures 0-500 VAC and requires 85-265 VAC auxiliary power.
Overvoltage uses output relay OUT1, while undervoltage, phase sequence detection, and three-phase imbalance protection share output relay OUT2.
It supports standard Modbus RTU over an RS485 bus, with up to 32 terminals.