Danfoss MCHE MicroChannel Heat Exchanger Installation and Maintenance Manual

This manual provides installation and maintenance instructions for MicroChannel heat exchangers (MCHE). This manual is intended for use by all users, including end users, installers, maintenance personnel, service personnel and system designers.


Danfoss MCHE MicroChannel Heat Exchanger Installation and Maintenance Manual - cover page
Brand
Danfoss
Category
Other
Document type
Service Manual
Language
English
Pages
10
File format
PDF
File size
2.1 MB
Published
03 November, 2023
Updated
03 November, 2023
MD5 checksum
D11007F18E69F9F599D9EAF7FE0DC655

About this manual

This guide provides instructions for the installation, operation, and maintenance of Danfoss MicroChannel Heat Exchangers (MCHEs). It emphasizes the importance of reading the manual before commencing work and outlines safety symbols and general responsibilities for personnel handling the units.

What's inside

  • Introduction
  • Storage and working environments
  • Bending procedure
  • Installation
  • Leak repair
  • Coating
  • Maintenance

Frequently asked questions

What is the storage temperature range for MCHEs?

The storage temperature range is -40 °C to 121°C (-40°F to 250°F).

How far should the fan be from the MCHE coil?

The distance between the MCHE and fan is recommended to be at least 15 times the width/depth of the MCHE coil when possible.

What is the recommended minimum pipe length after the brazing joint?

The recommended pipe length after the brazing joint should be greater than or equal to 70 mm.

How can galvanic corrosion be prevented between the MCHE and other metals?

Use plastic, rubber, or foam to isolate the aluminum coil from dissimilar metals.