Vacon NX AC Drives OPTCJ BACnet Option Board User Manual

This document is the Chinese version of the Vacon NX AC drives OPTCJ BACnet option board user manual, which introduces the technical data, wiring connection, installation and commissioning of the BACnet option board for Vacon NX AC drives


Vacon NX AC Drives OPTCJ BACnet Option Board User Manual - cover page
Brand
Vacon
Document type
User Manual
Language
English
Pages
26
File format
PDF
File size
1 MB
Published
03 November, 2023
Updated
03 November, 2023
MD5 checksum
5A13D16A9022DE811360BA5EA6EA6677

About this manual

This manual provides detailed instructions for installing and commissioning the Vacon NX AC drives BACnet option board. It covers technical data, fieldbus board layout, grounding methods, LED indicators, and fault tracking. The document includes specifications for communication, environmental conditions, and software version compatibility. It also explains how to configure BACnet parameters such as MAC address, baud rate, and instance number. Safety warnings are included regarding high voltage risks during installation.

What's inside

  • General Info
  • BACnet Option Board Technical Data
  • BACnet Fieldbus Board Layout and Connections
  • Grounding Cable Shield
  • LED Indications
  • Installation of Vacon NX BACnet Board
  • Commissioning
  • Fault Tracking

Specifications

InterfacePluggable connector (5.08mm)
Data Transfer MethodRS-485 MS/TP, half-duplex
Transfer CableTwisted pair (1 pair and shield)
Electrical Isolation500 VDC
Baud Rate9600, 19200, 38400 and 76800 baud
MAC Addresses1 to 127
Ambient Operating Temperature-10°C…55°C
Storing Temperature-40°C…60°C
Humidity<95%, no condensation allowed
AltitudeMax. 1000 m

Frequently asked questions

Where should the BACnet option board be installed?

It shall be installed in slot E on the control board of the frequency converter.

What are the supported system software versions for the OPT-CJ BACnet option board?

Supported versions include NXL NXL00005V149.VCN, NXS NXS00001V161.VCN, and NXP NXP00002V160.VCN.

How should the cable shield be grounded?

Grounding by clamping the cable to the converter frame is recommended, especially for short distances or last device on the net.

What is the default communication timeout?

The default communication timeout is 10 seconds, available from system software versions NXL00005V254.VCN, NXS00001V167.VCN, and NXP00002V168.VCN.

Download PDF (1 MB)