Electrical installation guide of VEX340H with EXact con- trol system.
Electrical installation guide for the EXHAUSTO VEX340H air handling unit with the EXact control system. Chapter 1 and 2 cover the connection diagram for supply voltage and the connection box, termination, and the cable plan.
The later sections cover installation of the VEX, connections in the connection box, dimensioning and electrical installation, electrical components and terminal blocks, connecting shielded cable to MODBUS, and service connection of an additional HMI control panel. The guide states that work must be performed by an authorised electrician and that the supply voltage must be disconnected before the service doors are opened.
| Supply voltage (VEX340) | 1 x 230 V + N + PE |
|---|---|
| Dimensioned power consumption (max. phase current) | 12.5 A |
| Maximum fuse rating | 63 A (gG/gL) |
| Maximum short-circuit current | 10 kA in accordance with EN60947.2 |
| MODBUS cable type | Shielded cable 2 x 2 x 0.25 |
The work must be performed by an authorised electrician, in accordance with locally applicable regulations and legislation.
The supply voltage must be disconnected at the isolation switch before the service doors are opened.
The maximum fuse rating is 63 A (gG/gL).
MODBUS requires shielded cable 2 x 2 x 0.25.