Exhausto VEX33DM / VEX35DV / VEX35-2DV Electric Heat Plate Installation Guide

This is a PDF installation manual for VEX33DM / VEX35DV / VEX35-2DV electric heat plate, including the specifications, features, installation steps and other information of the heat plate


Exhausto VEX33DM / VEX35DV / VEX35-2DV Electric Heat Plate Installation Guide - cover page
Brand
Exhausto
Document type
Installation Guide
Language
DA
Pages
4
File format
PDF
File size
873 KB
Published
18 October, 2023
Updated
18 October, 2023
MD5 checksum
95AF35DE1A35D2D2F7DBC2151E197864

About this manual

This guide provides installation instructions for Exhausto’s electric heat plates, designed for use in comfort ventilation systems. The plates are made of aluminum-zinc plate and stainless steel heating elements, with built-in safety thermostats. Installation must follow specific electrical and positioning guidelines, including minimum airflow and exclusion from explosive environments. The document includes wiring diagrams and component specifications for EKA and EKA NIS models.

What's inside

  • Description
  • Installation
  • Electrical Connection
  • Wiring Diagrams
  • Technical Specifications
  • Safety Instructions

Specifications

Maximum Air Temperature After Heater30 °C
Frequency50 Hz
EKA160300 Power300 Watt
EKA NIS1601000 Power1000 Watt

Frequently asked questions

Can the heater be mounted vertically or horizontally?

Yes, the heater can be mounted vertically or horizontally, but the electrical box must not be oriented downward.

What is the minimum airflow required through the heater?

The airflow must be at least 1.5 m/s.

What safety features does the heater have?

It has two thermostats: an automatic 50°C and a manual 100°C thermostat, and rubber seals on connection terminals.