Exhausto VEX350H/VEX360H Electrical Installation Guide

This document is the electrical installation guide for VEX350H/VEX360H, which introduces the wiring diagram, electrical connection and installation instructions of EXHAUSTO system automation EXact.


Exhausto VEX350H/VEX360H Electrical Installation Guide - cover page
Brand
Exhausto
Category
Industrial Robot
Document type
Installation Guide
Language
DA
Pages
16
File format
PDF
File size
2.9 MB
Published
18 October, 2023
Updated
18 October, 2023
MD5 checksum
18F190307E29D755D3DF384852997472

About this manual

This document serves as an electrical installation guide for the Exhausto VEX350H and VEX360H air handling units equipped with EXact automation. It provides detailed instructions on connecting the power supply, configuring the connection box, and integrating various accessories such as heating and cooling units via Modbus. The guide emphasizes safety protocols, including the requirement for work to be performed by authorized electricians and adherence to local regulations.

What's inside

  • Connection diagram for power supply
  • Installation of the VEX unit
  • Termination of the bus system
  • Cable plan for accessories
  • Electrical components and connection board
  • Power supply sizing and requirements
  • Modbus connection for accessories
  • Service connection for extra HMI panel

Specifications

VEX350 Max Phase Current11,2 A
VEX360 Max Phase Current18 A
Maximum Fuse Size63 A (gG/gL)
Leakage Currentup to 100 mA
Disconnection Timemax 0,3 sec

Frequently asked questions

Who is authorized to perform the electrical installation?

The work must be carried out by an authorized electrician in accordance with local laws and regulations.

What is the maximum fuse size allowed for the unit?

The fuse must not exceed a maximum size of 63 A (gG/gL).

What type of cable is required for the Modbus connection?

A shielded cable of type 2 x 2 x 0,25 is used for the Modbus connection.