Omron Controller Link Industrial Bus System Course

Controller Link is an industrial bus system developed by Omron. It supports fast communication between PLCs, PCs, and Terminals for plant or factory control and global process monitoring and process data exchange.


Omron Controller Link Industrial Bus System Course - cover page
Brand
Omron
Category
Automation control Equipment
Document type
Other
Language
Spanish
Pages
27
File format
PDF
File size
737 KB
Published
02 November, 2023
Updated
02 November, 2023
MD5 checksum
53D6B4CF9AAA01479733CC36EF54C6B6

About this manual

This Spanish course material presents Controller Link as a proprietary Omron industrial network that shares large amounts of information among PLCs, PCs and NS10/NS12 terminals. Nodes can communicate through automatic Data Link or through FINS messages and SEND/RECV commands, using token passing with a floating master.

Data Link can be automatic, with common areas for participating nodes, or manual, configured through CX-Net with flexible send areas and offsets. The material also covers node and system checks, error handling, optical fiber connections, communication cable references and the Bypass function. This manual is written in Spanish.

What's inside

  • Introduction
  • Unit configuration
  • Automatic Data Link
  • Manual startup
  • Node configuration
  • Information flow
  • System status check
  • Error handling
  • Optical fiber connection
  • Communication cables

Specifications

Maximum channels shared per node1000 channels
Maximum Data Link size for CS1/CJ112000 channels (2 areas)
Total channels shared in Data Link area62000 channels
Data Link area typesCIO, LR, DM, EM
Communication methodToken passing
Maximum node distance with 62.5/125 µm fiber2 km
Maximum node distance with 50/125 µm fiber1 km
Attenuation for 50/125 fiber3.0 dB/km
Bypass function power supply24 VDC

Frequently asked questions

What is Controller Link?

Controller Link is described as a proprietary Omron industrial network that shares large amounts of information among nodes such as PLCs, PCs and NS10/NS12 terminals.

What communication method does Controller Link use?

It uses token passing with a floating master, so the polling node generates the token and checks the bus.

How is manual Data Link configured?

Manual Data Link is configured through CX-Net; it allows flexible send areas, offsets and nodes that only send or only receive data.

What is the maximum fiber distance between nodes with 62.5/125 µm cable?

The maximum distance between nodes is 2 km when using 62.5/125 µm fiber cable.

Download PDF (737 KB)

More Omron Manuals


View all Omron manuals →