Controller Link is an industrial bus system developed by Omron. It supports fast communication between PLCs, PCs, and Terminals for plant or factory control and global process monitoring and process data exchange.
This Spanish course material presents Controller Link as a proprietary Omron industrial network that shares large amounts of information among PLCs, PCs and NS10/NS12 terminals. Nodes can communicate through automatic Data Link or through FINS messages and SEND/RECV commands, using token passing with a floating master.
Data Link can be automatic, with common areas for participating nodes, or manual, configured through CX-Net with flexible send areas and offsets. The material also covers node and system checks, error handling, optical fiber connections, communication cable references and the Bypass function. This manual is written in Spanish.
| Maximum channels shared per node | 1000 channels |
|---|---|
| Maximum Data Link size for CS1/CJ1 | 12000 channels (2 areas) |
| Total channels shared in Data Link area | 62000 channels |
| Data Link area types | CIO, LR, DM, EM |
| Communication method | Token passing |
| Maximum node distance with 62.5/125 µm fiber | 2 km |
| Maximum node distance with 50/125 µm fiber | 1 km |
| Attenuation for 50/125 fiber | 3.0 dB/km |
| Bypass function power supply | 24 VDC |
Controller Link is described as a proprietary Omron industrial network that shares large amounts of information among nodes such as PLCs, PCs and NS10/NS12 terminals.
It uses token passing with a floating master, so the polling node generates the token and checks the bus.
Manual Data Link is configured through CX-Net; it allows flexible send areas, offsets and nodes that only send or only receive data.
The maximum distance between nodes is 2 km when using 62.5/125 µm fiber cable.