This manual provides detailed instructions on unpacking, installation, operation, maintenance and service of the K4, K6, K9 series chillers.
The K4, K6, K9 Standard Models Instruction Manual, Issue v 10.5, is published by Applied Thermal Control Limited (ATC). It covers safety warnings, unpacking, site requirements, warranty registration, installation, operation and set point changes, maintenance and service, troubleshooting, return of goods, dimensions and performance, and appendices for water-cooled condenser and integral deionising cartridge options.
The manual describes the four functional elements of the chillers: refrigeration, fluid handling, electrical, and control. It also provides warnings and cautions for safe operation, service and installation.
| Operating ambient temperature | +4°C to +40°C, non-condensing |
|---|---|
| Minimum front and rear clearance | At least 500 mm |
| Pump fluid pressure | Up to 150 psi |
| Cooling water flow rate (water-cooled versions) | At least 10 litres per minute |
| Cooling water pressure (water-cooled versions) | Not less than 1 bar (15 psi) |
| Cooling water temperature (water-cooled versions) | 15°C |
| Supply voltage tolerance | –15% to +10% |
| Recommended fluid line internal diameter | Ideally at least 12 mm |
ATC provides a 2-year parts and 1-year labour return-to-base warranty from delivery as standard on new equipment, if installed and operated according to the manual.
It requires a non-condensing ambient from +4°C to +40°C; cooling capacity is lost above 30°C.
Contact ATC on +44(0)1530 839998 or [email protected], and have the model and serial number available.
Fluid lines should ideally have an internal diameter of at least 12 mm.