This guide covers the recommended set-up and configuration of the Schneider Electric Conext XW Pro Solar Hybrid Inverter/Charger 120/240V using the Conext System Control Panel.
This document provides step-by-step configuration instructions for integrating Schneider Electric's XW Pro inverter with KiloVault battery systems. It covers basic and advanced settings for different battery models including HLX, CHLX, HAB, and PLC. Settings are tailored for specific battery types and discharge depths, with notes on firmware limitations and alternative monitoring tools like InsightCloud. The guide also includes links to related manuals and SCP menu maps for reference.
| Battery Type | Gel (overridden by Advanced Settings) |
|---|---|
| Battery Capacity | 150Ah per HLX in Parallel |
| Max Charge Rate | Set to a percentage of 140A so that when added to the solar charge controller amperage, the sum is 100A (per HLX in parallel) |
| Recharge Voltage (80% DoD) | 51.0V |
| Low Battery Cut Out | 48.0V |
| High Battery Cut Out | 57.6V |
| Battery Type | AGM (overridden by custom settings) |
| Battery Capacity | 180Ah per 2100 PLC in parallel |
| Recharge Voltage (50% DoD) | 48.4V |
| Low Battery Cut Out | 48V |
| High Battery Cut Out | 60V |
| Battery Temperature Compensation | -3mV/°C |
As of this writing, the XW Pro’s High Battery Cut Out cannot be set lower than 58V. This has been suggested to Schneider as a firmware update.
The recommended depth of discharge for LiFePO4 batteries is 80%.
Select the XW Pro on the Select Device menu, then press and release the Enter and Up Arrow and Down Arrow simultaneously. Advanced Settings will appear at the top of the XW Pro Setup menu.
No, the XW Pro cannot be commissioned with the SCP because too many settings are not available.