This manual introduces the connection, usage precautions, parameters, protection functions, specifications and other information of the Mitsubishi General Inverter FR-F700 series
This is the application edition (应用篇) of the Mitsubishi FR-F700 series inverter operation manual, written in Chinese. It begins with safety information and cautions for handling, installation, wiring, trial operation, maintenance and disposal, and lists the FR-F700 models it applies to. The manual should be read together with the basic edition (基础篇) supplied in the same package.
The main body covers wiring of the main circuit and control circuit terminals, connection of separate option units, design of the electrical cabinet and noise, leakage current and harmonic countermeasures. Later chapters list parameters and describe torque adjustment, output frequency limits, V/f curve setting, frequency setting from external terminals, acceleration/deceleration times, motor protection and the assignment of external terminal functions.
| Ambient temperature (Normal Duty) | -10 °C to +50 °C (no freezing) |
|---|---|
| Ambient temperature (Light Duty) | -10 °C to +40 °C (no freezing) |
| Ambient humidity | 90% RH or less (no condensation) |
| Altitude and vibration | 1000 m or less, 5.9 m/s² or less |
| Permissible load | Three-phase squirrel-cage motor only |
It should be read together with the basic edition (基础篇) manual packed with the product.
Wait about 10 minutes after the power is switched off, then check the residual voltage with a tester such as a multimeter.
Only a three-phase squirrel-cage motor should be used as the load; connecting other electrical equipment to the output side may damage the equipment.