The AMDGH-X/F32□ series three-phase AC motor protector is a DSP-based, digitally set, digitally displayed, complete protection function, reliable protection performance, detection, display voltage, general current transformer detection current, isolated PROFIBUS communication interface.
The XWAM AMDGH-X/F32□ is a three-phase AC motor protection relay for motors with a rated voltage no higher than 1140 V at 50 Hz or 60 Hz, including motors with heavy starting loads and long starting times. It uses a DSP core with digital setting and digital display, detects current with a general-purpose current transformer, and provides an isolated PROFIBUS communication interface.
During normal operation, the main unit displays the motor's phase A, B, and C currents and voltage on five LED digits. When a fault such as phase loss, short circuit, ground fault, stall, overload, current imbalance, or underload occurs, the relay opens, the fault lamp lights, and a fault code and the fault-time currents and voltage are displayed. The document also describes keyboard operation with the R, M, up-arrow, and right-arrow keys, the PROFIBUS-DP interface, fault codes EE01 to EE07, and setup parameters. This manual is written in Chinese.
| Applicable voltage | Up to 1140 V, 50 Hz or 60 Hz |
|---|---|
| Working voltage | AC 85-265 V, DC 85-265 V |
| Power consumption | Less than 2 W |
| Detected voltage | AC 0-500 V |
| Ambient temperature | -20°C to 50°C |
| Relay contacts - AMDGH-X/F321 | 1 normally open and 1 normally closed contact |
| Relay contacts - AMDGH-X/F322 | 2 normally open and 2 normally closed contacts |
| PROFIBUS communication distance | Up to 1 km at 9600 BPS |
It provides protection against phase loss, short circuit, ground fault, stall, overload, current imbalance, and underload.
It displays the motor's phase A, B, and C currents and voltage.
EE01 indicates a ground fault.
Yes, its PROFIBUS-DP interface can communicate with S7-300 and S7-400 systems.