Fuji Duo Series Manual Motor Starters Accessories
This document covers optional accessories for Fuji Electric Duo Series manual motor starters using BM3R (45 mm wide) and BM3V (55 mm wide) frames. It lists auxiliary contact blocks, alarm and short-circuit alarm contact blocks, shunt and undervoltage trip devices, push-in lugs, terminal covers, and standard or emergency external operating handles with part numbers and prices.
The document also provides accessory specifications, dimensions and wiring diagrams for the listed contact blocks, trip devices and external operating handles.
| Compatible frame widths | BM3R: 45 mm; BM3V: 55 mm |
|---|---|
| Trip device rated insulation voltage | 690 VAC (IEC 60947); 600 VAC (UL 508) |
| Trip device ON-OFF operations | 5000 |
| Trip device operating time | 20 ms |
| Contact block standard | IEC 60947-5-1, UL 508 |
| Contact block minimum voltage and current | 17V / 5mA |
| External operating handle enclosure rating | IP54 |
It is required for screw mounting of the MMS and is supplied in quantities of 10 per package.
No. The document states that the shunt trip device cannot be used together with an undervoltage trip device.
They are used to operate an MMS installed inside a panel.
They operate only when the MMS has tripped due to a short-circuit.