This document is the user manual of ATV310 variable speed drive from Schneider Electric, which introduces the features and usage of the drive.
This manual provides detailed instructions for installing, configuring, and operating the ATV310 variable speed drive for asynchronous motors. It includes safety warnings, wiring guidelines, parameter programming, and troubleshooting steps. The document also references additional resources such as the Quick Start Guide and Modbus communication manuals for advanced setup.
The manual is structured to guide users through setup procedures, including preliminary recommendations, drive ratings, mounting, wiring, and factory configuration. It emphasizes safety precautions, especially regarding electrical hazards and motor operation, and includes diagnostic and maintenance sections for ongoing system support.
The drive supports 380 V to 460 V three-phase power with ratings from 0.37 kW to 11 kW.
You must wait 15 minutes to allow the DC bus capacitors to discharge before verifying the voltage.
The DC bus voltage can exceed 800Vdc even when the DC bus LED is not indicating absence of voltage.