Instruction manual for Anderson model RSP Sanitary Electronic Pressure Transmitter
This document is the instruction manual for the Anderson Instrument RSP Sanitary Electronic Pressure Transmitter. It covers the theory of operation, physical installation guidelines to prevent moisture damage, and detailed sensor and instrument wiring procedures. The manual specifies electrical requirements, including excitation voltage and loop resistance limits, and describes the optional integral LCD display installation.
| Excitation Voltage | 9-32 VDC (Absolute), 24 VDC Nominal |
|---|---|
| Output Signal | 4-20 mA DC |
| Loop Resistance | 0-750 ohms at 24 VDC |
| Accuracy | ±.5% of span, full scale |
| Housing Material | 304 Stainless Steel |
| Wetted Parts Material | 316L Stainless Steel |
| Storage Temperature | -40 to 150°F (-40 to 65°C) |
Anderson recommends a 24 gauge, 4 conductor, shielded cable, such as Belden #9534.
The sensor should be inspected at 6 month intervals to ensure physical integrity and wiring soundness.
Yes, the LCD display can be calibrated separately using a signal generator, but the decimal point location cannot be altered.